Description:
TRT-20 Transformer Turns Ratio Tester, adopts American IP67 Pelican case, light and portable. It is mainly used in transformer ratio group test, PT, CT transformer polarity test, which overcomes the shortcomings of traditional transformer bridge test. Test speed is fast, high accuracy. An essential tool for power system and transformer manufacturers.
Appearance Design
|
PELICAN Protector Case IP67
|
Processing Design
|
Imported materials, brushed metal panels, ultra-light, high-strength, ultra-corrosive titanium alloy screws, highlighting the quality
|
Screen Display
|
Large high-brightness color LCD screen, intuitive display, still clearly visible in strong sunlight
|
Range
|
0.9-10000
|
Accuracy |
±(reading×0.1%+2 words)(≤500)
|
±(reading×0.2%+2 words)(>500, ≤3000)
|
|
±(reading×0.3%+2 words)(>3000)
|
|
Resolution |
0.9-9.9999(0.0001)
|
100-999.99(0.01)
|
|
10-99.999(0.001)
|
|
1000-9999.9(0.1)
|
|
≥10000(1)
|
|
Store and Print
|
Built-in printer for easy data printing and real-time data storage
|
Power Supply
|
AC220V
|
Dimension
|
340*295*152mm
|
Weight
|
4kg
|